| Supply |
|
| Mains Voltage |
|
|
MVSxxxx-V02
|
3 x 2300 VAC (± 10%) |
|
MVSxxxx-V03
|
3 x 3300 VAC (± 10%) |
|
MVSxxxx-V04
|
3 x 4160 VAC (± 10%) |
|
MVSxxxx-V06
|
3 x 6600 VAC (± 10%) |
|
MVSxxxx-V07
|
3 x 7200 VAC (± 10%) |
|
MVSxxxx-V11
|
3 x 11000 VAC (± 10%) |
|
MVSxxxx-V13
|
3 x 13800 VAC (± 10%) |
| Control Voltage |
|
| MVSxxxx-xxx-C12 |
110 VAC to 130 VAC (+ 10% / - 15%) |
| |
or 220 VAC to 240 VAC (+ 10% / - 15%) |
| All models |
500 VA, single phase |
| Mains Frequency |
45 Hz to 66 Hz |
| Rated Power Frequency Withstand Voltage (Ud) |
| MVSxxxx-V02 ~ MVSxxxx-V04 |
11450 VAC |
| MVSxxxx-V06 ~ MVSxxxx-V07 |
20000 VAC |
| MVSxxxx-V11 ~ MVSxxxx-V13 |
35000 VAC
|
| Rated Lightning Impulse Withstand Voltage (BIL) - Overvoltage Category III (Up) |
| MVSxxxx-V02 ~ MVSxxxx-V07 |
45 kV |
| MVSxxxx-V11 |
85 kV |
| MVSxxxx-V13 |
95 kV
|
| Form Designation |
Bypassed semiconductor motor starter form 1 |
| Control Inputs |
|
| Start (Terminals C23, C24) |
24 VDC, 8 mA approx |
| Stop (Terminals C31, C32) |
24 VDC, 8 mA approx |
| Reset (Terminals C41, C42) |
24 VDC, 8 mA approx |
| Input A (Terminals C53, C54) |
24 VDC, 8 mA approx |
| Input B (Terminals C63, C64) |
24 VDC, 8 mA approx |
| Motor Thermistor (Terminals B4, B5) |
|
| Outputs |
|
| Relay Outputs |
10 A @ 250 VAC/ 360 VA |
| |
10 A @ 30 VDC resistive |
| Main Contactor (Terminals 13, 14) |
Normally Open |
| Bypass Contactor (Terminals 23, 24) |
Normally Open |
| Run Output/ PFC (Terminals 33, 34) |
Normally Open |
| Output Relay A (Terminals 43, 44) |
Normally Open |
| Output Relay B (Terminals 51, 52, 54) |
Changeover |
| Output Relay C (Terminals 61, 62, 64) |
Changeover |
| Analog Output (Terminals B10, B11) |
0-20 mA or 4-20 mA |
| Environmental |
|
| Degree of Protection |
|
| Power Assembly |
IP00 |
| Controller |
IP54/ NEMA 12 |
| Operating Temperature |
- 10 ˚C to + 60 ˚C |
| Storage Temperature |
- 25 ˚C to + 55 ˚C |
| |
- 25 ˚C to + 70 ˚C (< 24 hours) |
| Humidity |
5% to 95% Relative Humidity |
| Pollution Degree |
Pollution Degree 3 |
| Vibration |
Designed to IEC 60068 Test Fc Sinusoidal |
| |
4 Hz to 13.2 Hz: ± 1 mm displacement |
| |
13.2 Hz to 200 Hz: ± 0.7 g |
| EMC Emission |
|
| Equipment Class (EMC) |
Class A |
| Conducted Radio Frequency Emission |
10 kHz to 150 kHz: < 120 - 69 dB µV |
| |
0.15 MHz to 0.5 MHz: < 79 dB µV |
| |
0.5 MHz to 30 MHz: < 73 dB µV |
| Radiated Radio Frequency Emission |
0.15 MHz to 30 MHz: < 80-50 dB µV/m |
| |
30 MHz to 100 MHz: < 60-54 dB µV/m |
|
100 MHz to 2000 MHz: < 54 dB µV/m |
| |
|
| This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods. |
| EMC Immunity |
|
| Electrostatic Discharge |
6 kV contact discharge, 8 kV air discharge |
| Radio Frequency Electromagnetic Field |
80 MHz to 1000 MHz: 10 V/m |
| Fast Transients |
5/50 ns (main and control circuits) |
| |
2 kV line to earth, 1 kV line to line |
| Surges 1.2/50 µs (main and control circuits) |
2 kV line to earth, 1 kV line to line |
| Voltage dip and short time interruption |
5000 ms (at 0% nominal voltage) |
| |
(safe shutdown) |
| Short Circuit |
|
| Rated short-circuit current, symmetrical, fused (Class E2) |
|
| MVSxxxx-V02 ~ MVSxxxx-V07 |
48 kA |
| MVSxxxx-V11 ~ MVSxxxx-V13 |
75 kA
|
| Power Assembly (SCRs bypassed) |
20 W approx |
| Controller |
10 W approx |
| Standards Approvals |
|
| C√ |
EMC requirements |
| UL/ C-UL |
UL 508, UL 347 |
| CE |
EMC EU Directive |
| Marine |
Lloyd s Register |